Discontinued
140ACI04000 Modicon Quantum Analog Input Module, 16 Inputs
- MFR:
- Schneider Electric
- MFR #:
- 140ACI04000
- UPC:
- 785901334019
- Item #:
- 94033
Discontinued
140ACI04000 Modicon Quantum Analog Input Module, 16 Inputs
- MFR #:
- 140ACI04000
- UPC:
- 785901334019
- Item #:
- 94033
Schneider Electric Modicon® Quantum™ Analog Input Module, 16 Inputs, 16 bit Conversion Rate, 0 to 60 deg C
Manuals & Documentation
Features
- 1-pole low pass 3 dB at 15 Hz +/-20% filter
- Differential input
- 17 input words addressing requirement
- 30 mA absolute maximum input
- 250 Ohm input impedance
- +/-0.125% of full scale absolute accuracy error
- +/-0.0025% of full scale/deg C, <=0.005% of full scale/deg C accuracy drift according to temperature
- >-90 dB 60 Hz common mode rejection
- 1780 VAC for 60 s isolation between channel and bus
- 15 ms 2 or 4-wire update time
- Broken wire 4 to 20 mA fault type
- 360 mA bus current requirement
- 5 W power dissipation
- Standard module format
- 4 kV contacts conforming to IEC 801-2, 8 kV on air conforming to IEC 801-2 resistance to electrostatic discharge
- 10 V/m 80 to 1000 MHz conforming to IEC 801-3 resistance to electromagnetic fields
- -40 to 85 deg C ambient air temperature for storage
- 95% without condensation relative humidity
- <=5000 m operating altitude
- (1) LED green bus communication is present (active), (1) LED red external fault, 16 LEDs green channel is turned on, 16 LEDs red channel fault
| Manufacturer Part Number | 140ACI04000 |
| Stripped Manufacturer Part Number | 140ACI04000 |
| Brand | Schneider Electric |
| Manufacturer | Schneider Electric |
| UPC | 785901334019 |
| EAN | 3595861147997 |
| Temperature Rating | 0 to 60 deg C |
| Alternative Part Number | 8146553 |
| Manufacturer Item Status | Active |
| Country | USA |
| Warranty | 18 months |
| Standards Approvals | RoHS Compliant | CE Certified | FM Class 1 Division 2 | CSA C22.2 File No. 142 | cUL Listed | UL 508 | IEC 801-2-8 KV On Air IEC 801-2 | PROP65: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.p65warnings.ca.gov |
| Application | Modicon® Quantum™ Automation Platform Applications |
| Conversion Rate | 16 bit |
| Number Of Inputs | 16 |