Crouse-Hinds Eaton

ENR12201 Ark-Gard ENR Value 2-Gang Dead End Dust-Ignitionproof Explosionproof Raintight Interlocked Receptacle Assembly, 125 VAC, 20 A

MFR #:
ENR12201
UPC:
782274310992
Item #:
772471
Product Details

Ark-Gard® two receptacle incorporates three spring-loaded slide keys that prevent the receptacle face plate from being rotated until the ENP plug is fully inserted into the receptacle. To make the connection, the ENP plug is fully inserted and the receptacle face moved inward by pushing the plug forward. The plug is then rotated, closing the circuit. As rotation begins, the plug becomes locked in the receptacle and cannot be accidentally disengaged. In making or breaking the circuit, any resulting electrical arc is confined in the factory sealed chamber.

Manuals & Documentation

Features

  • Factory sealed chamber encloses the potential arcing components between two explosionproof threaded joints
  • These threads are specially coated to guarantee freedom of movement, which ensures ON/OFF action, no additional seals are required
  • One piece molded gasket seals cover plate and ENP plug when plug is inserted, providing full environmental protection at the receptacle face
  • Top hinged cover design with 45 deg downward angle provides superior protection in damp, wet and dirty locations
  • Field assembly is accomplished with standard tools
  • Use standard EDS back boxes

Specifications

Identifiers

Identifiers
Manufacturer Part Number
ENR12201
GTIN
00782274310992
Identifiers
UPC
782274310992

General Information

General Information
Manufacturer
Eaton
Brand
Crouse-Hinds
Country Of Origin
US
Warranty
Limited
General Information
Standards Approvals
ANSI Specified | UL 1010 | NEC Certified | CEC Certified | Class I, Division 1/2, Group B/C/D, Class II, Division 1/2, Group G, Class III | UL 943/1203 | CSA C22.2
Application
For portable electrical equipment such as compressors, tools, lighting systems, similar devices, also used in areas made hazardous by the presence of flammable vapors and gases or combustible dusts, damp, wet, dirty and corrosive location, refineries, chemical plants, LNG facilities, wastewater treatment facilities, drilling and exploration, industrial facilities, factories facility, power distribution and control applications
Includes
1/2 in Hub

Dimensions

Dimensions
Dimensions
7-9/16 in L x 8 in W x 6-23/32 in H

Technical Information

Technical Information
Amperage Rating
20 A
Series
ENR Value
Technical Information
Type
2-Gang Dead End Dust-Ignitionproof Explosionproof Raintight Interlocked
Voltage Rating
125 V AC