TeSys GV motor circuit breaker, 3 poles (3P), 0.63A/690V, for 3-phase motor applications 0.12-0.18kW@400V. It provides a thermal-magnetic protection with a thermal setting range 0.4-0.63A, magnetic tripping at 13xIn, high breaking capacity Icu 100kA@400V. Connection by spring terminals. Start-stop control by push-button guaranteed for 100 000 cycles AC-3. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX).

Manuals & Documentation
Catalog Number GV2ME043
Manufacturer Schneider Electric
Brand SCHNEIDER ELECTRIC
Warranty Description Contractual Warranty:18 months
Country of Origin France