Square D™ Schneider Electric

EXN150T3H Energy Efficient Transformer, 480 V Delta Primary, 208Y/120 V Secondary, 150 kVA Power Rating, 60 Hz, 3 ph

MFR #:
EXN150T3H
UPC:
785901357940
Item #:
574232
Product Details

EXN three phase low voltage dry type distribution transformers from Square D comply with DOE energy conservation standards and Natural Resources Canada (NRCan) minimum energy efficiency levels. This transformer is a 150kVA, 480V primary (three wire), 208Y/120V secondary (four wire) with aluminum windings with a 220 insulation system design for 150 degree C temperature rise. This transformer’s DOE 2016 and NRCan efficiency is a minimum of 98.83% at 35% loading and 75°C temperature. Terminals are designed to accommodate wire ranges sized for 125% of the secondary nameplate current and 250% of the primary nameplate current. The terminals allow for NEMA two hole lugs and wiring bending radius to align with the wire ranges and to allow for side and bottom access. Units are natural air cooled with exhaust vents located on the front only, allowing the transformers to be mounted with rear clearance to obstructions of ½ inch. Units are shipped as Type 2 for indoor installation, field convertible to Type 3R via weathershield for outdoor installation. The transformers are floor mounted but field accessories are available for wall or trapeze (ceiling) mounting. EX transformers have a low sound level, with a minimum of 3dB below NEMA Standard ST-20 requirements. Units are specifically designed to function with other Square D equipment; inrush is coordinated to meet identified breaker trip curves, and IZ levels allow for let through current to match AIR levels of panelboards. See product data sheets for these values.

Manuals & Documentation

Features

  • Space-saving design
  • Terminals sized to handle Square D equipment
  • Bending radius for side and bottom access

Specifications

Identifiers

Identifiers
Manufacturer Part Number
EXN150T3H
GTIN
00785901357940
Identifiers
UPC
785901357940

General Information

General Information
Manufacturer
Schneider Electric
Brand
Square D™
Country Of Origin
US
General Information
Standards Approvals
CSA C22.2 47 | UL File No. 1561 | RoHS Compliant | REACH Compliant | PROP65: This product can expose you to chemicals including, Phenyl Glycidyl Ether, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov.
Application
Low Voltage Electrical Distribution, Building Management and Security, Data Centers, Networks and Secure Power Applications

Dimensions

Dimensions
Dimensions
827 mm L x 855 mm W x 1031 mm H

Technical Information

Technical Information
Connection Type
4-Hole 11.1 mm NEMA Pad Primary, 4-Hole 11.1 mm NEMA Pad Secondary and 6-Hole 11.1 mm NEMA Pad Secondary
Efficiency
98.83 %
Enclosure Type
NEMA 2/3R/ST-20
Frequency Rating
60 Hz
Housing Material
Aluminum
Insulation
Class 220
Maximum Amperage Rating
180.42 A, 416.36 A, 150 kVA Operational/13.43 kA Let Through Current
Technical Information
Mounting Type
Ceiling/Floor
Number Of Taps
(2) 2.5% FCAN/(4) 2.5% FCBN
Phase
3
Power Rating
150
Primary Voltage
480 V Delta
Secondary Voltage
208Y/120 V
Temperature Rating
150 deg C Rise