GVAX116 TeSys Safety Undervoltage Trip, For Use With TeSys GV2ME Thermal Magnetic Motor Circuit Breaker, TeSys GV2 Manual Starter

MFR:
Schneider Electric
MFR #:
GVAX116
Item #:
339116

TeSys GV electrical trip, MN undervoltage release, 110-115V AC 60Hz, for motor circuit breakers GV2ME used in safety-related systems. It trips the circuit breaker when the control voltage drops below 0.35 Uc, possible opening between 0.35-0.7 Uc. Closing of the circuit breaker is only possible when the control voltage is applied in the range 0.85-1.1 Uc. To be mounted on right-hand side of the circuit breaker, connection by screw clamp terminals. Multi standards certified (IEC, UL, CSA, CCC, EAC, INRS, VDE 0113).

Manuals & Documentation
Catalog Number GVAX116
Manufacturer Schneider Electric
Brand SCHNEIDER ELECTRIC
Warranty Description Contractual Warranty:18 months
Country of Origin Czech Republic
Made in USA No
Color Dark Gray
RoHS URL https://checkaproduct.se.com/DistantRequestDispatcher.aspx?action=export&pid=608058&lang=en-us
GTIN 03389110346091
Cross Reference Products Schneider GV2AX116|Schneider GVAX116|Telemecan GVAX116