Discontinued
140ATI03000 Modicon Quantum Analog Input Module, 8 Inputs, 16 bit Resolution
- MFR #:
- 140ATI03000
- UPC:
- 785901792239
- Item #:
- 281244
140ATI03000 Modicon Quantum Analog Input Module, 8 Inputs, 16 bit Resolution
- MFR #:
- 140ATI03000
- UPC:
- 785901792239
- Item #:
- 281244
Product Details
Schneider Electric Modicon® Quantum™ Analog Input Module, 8 Inputs, 16 bit Resolution, 0 to 60 deg C
Manuals & Documentation
Features
- Notch filter 3 dB at 50/60 Hz, single pole low pass 3 dB at 20 Hz filter
- 10-input words addressing requirement
- >1 MOhm input impedance
- 0.15 UV/deg C +0.0015% of reading/deg C maximum low level voltage accuracy drift according to temperature
- >=120 dB 50/60 Hz common mode rejection
- 1780 VAC for 60 s, 2500 VDC for 60 s isolation between channel and bus
- 220 VAC, 300 VDC isolation between channel
- 1000 ms update time
- Broken wire, over tacking scale fault type
- Internal 0 to 60 deg C cold junction compensation
- 280 mA bus current requirement
- 1.5 W power consumption
- Standard module format
- 4 kV contacts conforming to IEC 801-2, 8 kV on air conforming to IEC 801-2 resistance to electrostatic discharge
- 10 V/m 80 to 1000 MHz conforming to IEC 801-3 resistance to electromagnetic fields
- -40 to 85 deg C ambient air temperature for storage
- 95% without condensation relative humidity
- <=5000 m operating altitude
- (1) LED green bus communication is present (active), (1) LED red external fault, 8 LEDs green channel is turned on, 8 LEDs red channel fault
- Thermocouple type B, E, J, K, R, S, T, MV
Specifications
| Manufacturer Part Number | 140ATI03000 |
| Brand | Schneider Electric |
| Manufacturer | Schneider Electric |
| UPC | 785901792239 |
| Country Of Origin | FR |
| Temperature Rating | 0 to 60 deg C |
| Manufacturer Item Status | Discontinued |
| Country | USA |
| Warranty | 18 months |
| Standards Approvals | ARRA Compliant | Buy American Act Compliant | RoHS Compliant | CE Marked | FM Class 1 Div 2 | CSA C22.2 No. 142 | cUL Listed | UL 508 | PROP65: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.p65Warnings.ca.gov |
| Application | Modicon® Quantum™ Automation Platform Applications |
| Number Of Inputs | 8 |
| Resolution | 16 bit |