Veris Industries Schneider Electric

LVCT01204S PowerLogic Split core balance, 1200 A primary, 0.333 V, 50/60 Hz

MFR #:
LVCT01204S
Item #:
770209
Product Details

This low-voltage split-core current transformer is part of PowerLogic BCPM (Branch Circuit Power Meter). It is Ideal for retrofit applications with Schneider Electric energy meters which accept low voltage current transducer input It is rated for a 1200A circuit. 0.333 V output, size 4. Split core opening is 62 mm x 201 mm.

Manuals & Documentation

Features

  • The BCPM series monitors up to 84 branch circuits and the incoming power mains to provide information on each branch circuit
  • Full alarming capabilities ensure that potential issues are dealt with before they become problems
  • The BCPM series offers flexibility for both new construction and retrofit installations, plus a wide variety of communication options, including Ethernet
  • It has exceptional dynamic range and accuracy, and optional feature sets to meet the energy challenges of even the most mission critical facilities
  • The BCPM series offers both solid-core and a split-core CT options
  • The metering unit can be ordered in one of three available feature sets: Advanced/Advanced Ethernet: Power and energy per circuit and mains
  • Intermediate: Current per circuit, power and energy per mains
  • Basic: Current only per circuit and mains
  • Characteristics
  • Monitor 42 or 84 circuits with 2 or 4 solid-core CT strips
  • Monitor up to 84 circuits with individual split-core CTs
  • Supports single phase and 3-phase circuit metering
  • Monitor mains with two sets of inputs for four auxiliary CTs
  • Set alarm levels at High-High, High, Low and Low-Low as a percent of breaker rating, to ensure you get an alarm before a breaker trip occurs
  • The PowerLogic Branch Circuit Power Meter (BCPM) series helps you: Reduce energy costs
  • Improve continuity of service for optimal management of your electrical installation and increased productivity
  • Maximize uptime and avoid outages
  • 0.333 V output voltage
  • Split core balance current transformer type

Specifications

Identifiers

Identifiers
Manufacturer Part Number
LVCT01204S
Identifiers
EAN
3606480299698

General Information

General Information
Manufacturer
Schneider Electric
Brand
Veris Industries
Country Of Origin
US
General Information
Warranty
18 months
Standards Approvals
PROP65: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
Application
For a 1200A circuit, For retrofit applications with Schneider Electric energy meters which accept low voltage current

Dimensions

Dimensions
Dimensions
5.47 in H x 5.94 in W x 1.18 in D

Technical Information

Technical Information
Accuracy
1 %
Connection Type
Cable
Frequency Rating
50/60 Hz
Primary Current
1200 A
Technical Information
Series
PowerLogic
Temperature Rating
-15 to 60 deg C
Type
Split core balance
Voltage Rating
0.333 V