Square D™ Schneider Electric

8536SEG1V03 General Purpose Type S Starter, 220/240 VAC V Coil, Non-Reversing Action, 3 Poles, NEMA 1 Enclosure

MFR #:
8536SEG1V03
UPC:
785901788829
Item #:
66099
Product Details

Type S NEMA motor starters are used for full voltage starting and stopping of AC squirrel cage motors. Type S motor starters have ratings up to 810 amperes. This 3 pole NEMA Size 3 non-reversing starter has a 90 ampere rating. This NEMA Size 3 motor starter has 3 phase ratings of 25 HP at 200 VAC, 30 HP at 230 VAC and 50 HP at 460 and 575 VAC. This non-reversing NEMA motor starter has a melting alloy type overload relay that uses Type CC thermal units to sense over current conditions. This NEMA starter has a 5 kA maximum SCCR (Short Circuit Current Rating) per UL508A when protected by an appropriate circuit breaker or fuse. Type S motor starters are available with replaceable coils in a wide variety of voltages. This starter has a 220/240 VAC 50/60 Hz operating coil wired for common control. A painted sheet steel NEMA 1 general purpose enclosure is used to protect this starter. Enclosure is 21.81 inches tall, 11.44 inches wide and 8.38 inches deep. A wide variety of accessories are available for Type S starters. Type S non-reversing NEMA motor starters are UL listed and CSA certified.

Manuals & Documentation

Features

  • Flexiblewith four overload relays types
  • Customizablewith hundreds of combinations
  • Streamline installation, wiring, maintenance and field modifications
  • Reliable build for long mechanical life and electrical endurance

Specifications

Identifiers

Identifiers
Manufacturer Part Number
8536SEG1V03
GTIN
00785901788829
Identifiers
UPC
785901788829
EAN
0785901788829

General Information

General Information
Manufacturer
Schneider Electric
Brand
Square Dâ„¢
Country Of Origin
MX
General Information
Warranty
18 Months
Standards Approvals
UL Listed | CSA Certified | ECCN: EAR99 | PROP65: This product can expose you to chemicals including: Antimony oxide and Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Application
For full voltage starting, stopping of AC squirrel cage motor and indoor applications

Dimensions

Dimensions
Dimensions
11-7/16 in W x 8-3/8 in D x 21-13/16 in H

Technical Information

Technical Information
Action
Non-Reversing
Amperage Rating
90 A
Coil Voltage
220/240 V AC
Connection Type
Screw Clamp/Box Lug
Enclosure Type
NEMA 1
Frequency Rating
50/60 Hz
Material
Sheet Steel
Motor Power
50 hp
Technical Information
Number Of Poles
3
Overload Relay
Thermal Melting Alloy
Phase
3
Reset Type
Thermal Melting Alloy
Starting Modes
Magnetic
Type
General Purpose Type S
Voltage Rating
600 V AC