Square D™ Schneider Electric

EXN75T3HCU PH Series, 480 V primary, 208Y/120 V secondary, 3 phase

MFR #:
EXN75T3HCU
UPC:
785901830863
Item #:
627182
Product Details

EXN three phase low voltage dry type distribution transformers from Square D comply with DOE energy conservation standards and Natural Resources Canada (NRCan) minimum energy efficiency levels. This transformer is a 75kVA, 480V primary (three wire), 208Y/120V secondary (four wire) with copper windings with a 220 insulation system design for 150 degree C temperature rise. This transformer’s DOE 2016 and NRCan efficiency is a minimum of 98.60% at 35% loading and 75°C temperature. Terminals are designed to accommodate wire ranges sized for 125% of the secondary nameplate current and 250% of the primary nameplate current. The terminals allow for NEMA two hole lugs and wiring bending radius to align with the wire ranges and to allow for side and bottom access. Units are natural air cooled with exhaust vents located on the front only, allowing the transformers to be mounted with rear clearance to obstructions of ½ inch. Units are shipped as Type 2 for indoor installation, field convertible to Type 3R via weathershield for outdoor installation. The transformers are floor mounted but field accessories are available for wall or trapeze (ceiling) mounting. EX transformers have a low sound level, with a minimum of 3dB below NEMA Standard ST-20 requirements. Units are specifically designed to function with other Square D equipment; inrush is coordinated to meet identified breaker trip curves, and IZ levels allow for let through current to match AIR levels of panelboards. See product data sheets for these values.

Manuals & Documentation

Features

  • Space-saving design
  • Terminals sized to handle Square D equipment
  • Bending radius for side and bottom access
  • This circuit breaker provides 10 kA breaking capacity

Specifications

Identifiers

Identifiers
Manufacturer Part Number
EXN75T3HCU
Identifiers
UPC
785901830863

General Information

General Information
Manufacturer
Schneider Electric
Brand
Square D™
Country Of Origin
MX
General Information
Standards Approvals
PROP65: This product can expose you to chemicals including: Phenyl Glycidyl Ether, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov | UL 1561CSA C22.2 No 47NEMA ST-20
Application
For designing with the minimum AIC Panels available

Dimensions

Dimensions
Dimensions
33.50 in H x 30.08 in W x 27.44 in D

Technical Information

Technical Information
Efficiency
98.65 % at 35 % load factor
Phase
3
Primary Voltage
480 V
Technical Information
Secondary Voltage
208Y/120 V
Series
PH Series
Temperature Rating
40 deg C