MA4IMA241 Surgelogic IMA Series Surge Protection Module, 480Y/277 V AC, 50/60 Hz, 3 Poles, 200 kA SCCR, 3 Phase
- MFR #:
- MA4IMA241
- UPC:
- 785901075196
- Item #:
- 586238
MA4IMA241 Surgelogic IMA Series Surge Protection Module, 480Y/277 V AC, 50/60 Hz, 3 Poles, 200 kA SCCR, 3 Phase
- MFR #:
- MA4IMA241
- UPC:
- 785901075196
- Item #:
- 586238
Product Details
Surgelogic™ EMA replacement modules surge protective devices are apart of modular brick parallel device. The EBA device has multi-stage suppression circuits consisting of field-proven, fast-acting metal oxide varistors (MOVs). These systems provide suppression, enchanced EFI/RFI filtering for all critical modes inside electrical equipment, and shorter lead lengths with superior SPD performance. This surge protection device is 3 phase, 4-wire + ground, 480Y/277 V, 240 kA surge current per phase, and short circuit current rating of 200 kA. They provide better performance with a diagnostic interface with push to test switches, red and green status LEDs, module status LEDs per mode, dry contacts, audible alarm with disable switch, and a surge counter. The device is engineered to UL 489 11th Edition, type 1 SPD and complies with UL 96A 12th Edition Master Label for Lightning Protection Systems.
Manuals & Documentation
Features
- Surgelogic provides high performance surge suppression even in severe electrical conditions
- Externally mounted replacement module design allows for fast, easy service or replacement
- Noise filtering as well as transient surge suppression
- Fusing uses Thermal Cut-Off circuitry to isolate the SPD during severe overvoltages
Specifications
Identifiers
| Manufacturer Part Number |
MA4IMA241
|
|---|---|
| GTIN |
00785901075196
|
| UPC |
785901075196
|
|---|---|
| EAN |
0785901075196
|
General Information
| Manufacturer |
Schneider Electric
|
|---|---|
| Brand |
Square D™
|
| Country Of Origin |
MX
|
| Standards Approvals |
ANSI/IEEE C62.41/C62.45 | CSA C22.2 File No. 8:1986 | NEC 285 | UL 1449 | PROP65: This product can expose you to chemicals including: DINP and DIDP which is known to the State of California to cause Carcinogen and Reproductive harm For more information go to www.p65warnings.ca.gov
|
|---|---|
| Application |
For low voltage products and systems, building automation and control, industrial automation and control, critical power, cooling and racks
|
| Includes |
Alarm Enable/Disable Switch
|
Dimensions
| Dimensions |
82.8 mm W x 68.3 mm D x 158.8 mm H
|
|---|
Technical Information
| Color |
Black
|
|---|---|
| Electrical Ratings |
480Y/277 V AC
|
| Enclosure Type |
NEMA 1
|
| Environmental Conditions |
149 deg F Operating Temperature
|
| Frequency Rating |
50/60 Hz
|
| Indicator Type |
Alarm/LED Status Light
|
| Material |
Plastic
|
| Mounting Type |
Panel
|
| Nominal Discharge Current |
20 kA
|
|---|---|
| Number Of Poles |
3
|
| Number Of Wires |
4
|
| Peak Surge Current |
240 kA
|
| Phase |
3
|
| Series |
IMA Series
|
| Short Circuit Current Rating |
200 kA
|