9050JCK60V20 Type JCK Timing Relay, 1 to 999 min Setting, 240 V AC, 8 Pin, 2NO-2NC 2 Form C DPDT Contact
- MFR #:
- 9050JCK60V20
- UPC:
- 785901053866
- Item #:
- 171437
9050JCK60V20 Type JCK Timing Relay, 1 to 999 min Setting, 240 V AC, 8 Pin, 2NO-2NC 2 Form C DPDT Contact
- MFR #:
- 9050JCK60V20
- UPC:
- 785901053866
- Item #:
- 171437
Product Details
9050JCK plug in timers are designed to provide low cost timing in a plug in housing. This timer has an on delay timing mode. When the input voltage is applied, the time delay begins. Relay contacts change state after time delay is complete. When the input voltage is removed, contacts return to their shelf state. The timing range of 0.5 seconds to 999 hours is easily adjustable with thumb wheels on the top of the timer. This plug in timer plugs into an 8501NR51 or 8501NR52 relay socket. These relay sockets can be mounted on 35 mm DIN 3 mounting track or directly to a panel. All wiring is made to the relay socket. The DPDT contacts are rated 10 amperes resistive at 120 VAC, 240 VAC and 30 VDC, 3 amperes inductive at 120 VAC, 240 VAC and 30 VDC, 1/3 HP on the NC contacts at 120 VAC and 240 VAC, 1/2 HP on the NO contacts at 120 VAC and 240 VAC. This plug in timer is powered up with 120 VAC / 110 VDC. 9050JCK plug in timers are UL listed when the proper 8501NR relay socket is used, UL component recognized and CSA certified.
Manuals & Documentation
Features
- Easy to set up and install
- Wide range of operating temperature from -18.4F to 150.8F
Specifications
Identifiers
| Manufacturer Part Number |
9050JCK60V20
|
|---|---|
| GTIN |
00785901053866
|
| UPC |
785901053866
|
|---|---|
| EAN |
0785901053866
|
General Information
| Manufacturer |
Schneider Electric
|
|---|---|
| Brand |
Square Dâ„¢
|
| Country Of Origin |
MX
|
| Warranty |
18 months
|
|---|---|
| Standards Approvals |
CE Certified | CSA File No. LR60905/Class 321104 | ECCN: EAR99 | RoHS Compliant | UL File No. E78351 CCN NLDX | UL Recognized
|
| Application |
8501NR51, 8501NR52
|
Dimensions
| Dimensions |
44 mm W x 60 mm D x 91 mm H
|
|---|
Technical Information
| Amperage Rating |
10 A
|
|---|---|
| Coil Voltage |
120 V AC
|
| Contact Form |
2NO-2NC 2 Form C DPDT
|
| Electrical Connections |
Tubular
|
| Horsepower |
1/2 hp
|
| Mounting Type |
Socket
|
| Number Of Pins |
8
|
| Operation Mode |
On-Delay
|
|---|---|
| Series |
9050
|
| Temperature Rating |
-18 to 150 deg F
|
| Time Setting |
1 to 999 min
|
| Type |
Type JCK
|
| Voltage Rating |
240 V AC
|