Product Details
The 9012G pressure switches are UL listed and CSA certified as industrial control equipment. They are used to interface pneumatic or hydraulic systems with electrical control systems by opening or closing electrical contacts in response to pressure changes in the system. They have outstanding repeatability and drift performance. Their efficient design uses durable, low mass components for excellent performance under heavy duty vibration and shock conditions.
Manuals & Documentation
Features
- High shock-resistance
- High set-point stability
- Internal or external range adjustment
- No drain line required
- Dual numerical range scale (psi and kPa)
- Diaphragms of FKM fluorocarbon or ethylene propylene are available as well as stainless steel flanges
- 2 (NC NO), DPDT-DB, Form ZZ, snap action, silver nickel contacts
- -40 to 250 deg F hydraulic oil, air, non-corrosive liquid and non-corrosive gas
- 1/4 in 18 NPTF conforming to UL 508 fluid connection
- Regulation between 2 thresholds, adjustable differential scale
- 8 screw terminal blocks
- 22 to 12 AWG electrical connection
- Zinc plated steel flange
- Nitrile (Buna-N) diaphragm
- 3.5 to 15 psi +/-2.5% full scale approx differential at mid range
- 1/2 in NPT conduit entrance cable entry
- Die cast aluminum alloy housing
- Panel mounting
- 75 psi system pressure
- Adjustable differential scale
Specifications
| Manufacturer Part Number | 9012GAW24 |
| Brand | Square Dâ„¢ |
| Manufacturer | Schneider Electric |
| UPC | 785901024781 |
| EAN | 0785901024781 |
| Country Of Origin | MX |
| Dimensions | 3.5 in W x 2.63 in D x 5.55 in H |
| Enclosure Type | NEMA 4/4X/13 |
| Housing Material | Aluminum |
| Series | 9012G |
| Temperature Rating | -10 to 185 deg F |
| Type | Electromechanical Single Stage |
| Alternative Part Number | 8152552 |
| Manufacturer Item Status | Active |
| Country | USA |
| Standards Approvals | RoHS Compliant | UL 508 E12442 CCN NOWT | CSA LR26817 Class 3218 02 | CE Marked | IEC Certified | PROP65: This product can expose you to chemicals including: Diisononyl phthalate (DINP), which is known to the State of California to cause cancer and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.p65Warnings.ca.gov |
| Application | Compressed Air Systems, HVAC Equipment, Chillers, Pumping Systems, Machine Tools, Stamping Presses, Automatic Grinders, Welders, Process Equipment, Molding Machines, Indoor/Outdoor and General Purpose Applications and Regulation Between 2 Thresholds |
| Connection Type | NPT Conduit/Screw Clamp |
| Contact Configuration | 2NO-2NC |
| Contact Rating | 10 A at 480 V AC |
| Diaphragm Material | Nitrile |
| Differential | 3.5 to 15 psi |
| Maximum Pressure | 240 psi |
| Operating Cycles | 120 cpm |
| Pressure Rating | 1.5 to 75 psi |