Square D™ Schneider Electric

8536SCG3V01S Type S Starter, 24 VAC V Coil, Non-Reversing Action, 3 Poles, NEMA 1 Enclosure

MFR #:
8536SCG3V01S
UPC:
785901458470
Item #:
101297
Product Details

Type S NEMA motor starters are used for full voltage starting and stopping of AC squirrel cage motors. Type S motor starters have ratings up to 810 amperes. This 3 pole NEMA Size 1 non-reversing starter has a 27 ampere rating. This NEMA Size 1 motor starter has 3 phase ratings of 7.5 HP at 200 and 230 VAC and 10 HP at 460 and 575 VAC. This non-reversing NEMA motor starter has a melting alloy type overload relay that uses Type B thermal units to sense over current conditions. This NEMA starter has a 5 kA maximum SCCR (Short Circuit Current Rating) per UL508A when protected by an appropriate circuit breaker or fuse. Type S motor starters are available with replaceable coils in a wide variety of voltages. This starter has a 24 VAC 60 Hz operating coil wired for separate control. A painted sheet steel NEMA 1 general purpose enclosure is used to protect this starter. Enclosure is 10.00 inches tall, 6.00 inches wide and 5.56 inches deep. A wide variety of accessories are available for Type S starters. Type S non-reversing NEMA motor starters are UL listed and CSA certified.

Manuals & Documentation

Features

  • Flexiblewith four overload relays types
  • Customizablewith hundreds of combinations
  • Streamline installation, wiring, maintenance and field modifications
  • Reliable build for long mechanical life and electrical endurance

Specifications

Identifiers

Identifiers
Manufacturer Part Number
8536SCG3V01S
GTIN
00785901458470
Identifiers
UPC
785901458470
EAN
0785901458470

General Information

General Information
Manufacturer
Schneider Electric
Brand
Square Dâ„¢
Country Of Origin
US
Warranty
18 Months
General Information
Standards Approvals
CE Certified | IEC 947-4-1 | CSA 60905 Class 3211-04 | ECCN: EAR99 | UL File No. E78351 Guide No. NLDX | PROP65: This product can expose you to chemicals including: Antimony oxide and Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Application
Starting and Stopping of AC Squirrel Cage Motors, Construction, Infrastructure, Industrial Markets, Commercial Office Buildings and Building Automation Applications
Includes
Separate Control Circuit

Dimensions

Dimensions
Dimensions
5.98 in W x 5.55 in D x 10 in H

Technical Information

Technical Information
Action
Non-Reversing
Amperage Rating
27 A
Coil Voltage
24 V AC
Connection Type
Screw Clamp
Enclosure Type
NEMA 1
Frequency Rating
50/60 Hz
Material
Sheet Steel
Motor Power
7-1/2 hp at 200/230 VAC/10 hp at 460/575 VAC
Number Of Poles
3
Operating Cycles
10 cpm
Technical Information
Operating Temperature
0 to 40 deg C
Overload Relay
Thermal Melting Alloy
Phase
3
Reset Type
(3) Thermal Melting Alloy
Series
8536
Starting Modes
Magnetic
Type
Type S
Voltage Rating
600 V AC
Wattage
5.5 kW at 200/230 V AC/7.5 kW at 460/575 V AC