Sign in or register to view your pricing and inventory.

Genesis Cable 44021004 2 Wire FPLR-CL2R Shielded Fire Alarm Jacketed Cable; 18 AWG, Red, 1000 ft Reel

  • Genesis Cable 44021004 Genesis Cable 44021004 2 Wire FPLR-CL2R Shielded Fire Alarm Jacketed Cable; 18 AWG, Red, 1000 ft Reel
  • Genesis Cable 44021004 2 Wire FPLR-CL2R Shielded Fire Alarm Jacketed Cable; 18 AWG, Red, 1000 ft Reel
Manufacturer: Genesis Cable
Mfr. #: 44021004
Item #: 242444
UPC: 619172018609
Login for Availability
Your Price:

Product Details

Sunlight resistant, moisture resistant, abrasion resistant

0.001 Inch thick aluminum/mylar shield

2 Inch nominal lay length

Detailed Description: Genesis Cable FPLR-CL2R Shielded fire alarm jacketed cable in red/black color made of polyvinyl-chloride for durability. It has conductors size of 18 AWG that is made of bare copper and 0.006 Inchinsulation material that is made of thick polypropylene for durability. Cable comes with 0.001-Inch thick aluminum/mylar shield with 24 AWG solid tinned-copper drain wire is applied overall the assembled conductors. It is available in 1000 ft tangle-free boxes and has a outer diameter of 0.138 inches. Cable has a voltage rating of 300 Volts and temperature rating of -20 to 75 deg C. It is ideal for use with all power-limited circuits except those in plenums and wiring of fire-protective signaling circuits.

Product Specification

Application For Use with All Power-Limited Circuits Except Those in Plenums, Wiring of Fire-Protective Signaling Circuits
Brand Genesis Cable
Capacitance 42 pF/ft
Catalog Description Honeywell Cable 4402-10-04 Fire Alarm Cable, Number Of Conductors: 2, Conductor Size: 18 AWG, Solid Bare Copper, Outside Diameter: 0.138 IN, 300 V, Resistance: 6.5 OHM/100 MR At 20 DEG C, -20 To 75 DEG C, Insulation Material: Polypropylene, Jacket Material: PVC, Shield: 0.001 IN Thick Aluminum/Mylar (Overall Shielded), Red, Insulation: Black/Red, 1000 FT Length, Insulation Thickness : 0.006 IN, Insulation Diameter: 0.052 IN, Lay Length: 2 IN, 24 AWG Solid Tinned Copper Drain Wire, Jacket Thickness: 1/64 IN, Impedance: 36 OHM, Capacitance: 42 PFD/FT, UL Standards 1424, NEC Article 760 Type FPLR And UL Standards 13, NEC Article 725 Type CL2R; Flame Rating: UL 1666 (Riser), C(UL) FT4, RoHS Compliant, For Use With all Power-Limited Circuits Except Those in Plenums, Wiring of Fire-Protective Signaling Circuits
Conductor Material Copper
Conductor Size 18 AWG
Country Of Origin US
Environmental Conditions UL 1666 Riser, C(UL) FT4 Flame Rating
EU RoHS Indicator Y
Finish 2 Red
GTIN 00619172018609
Insulation Material Polypropylene
Insulation Thickness 0.006 Inch
Item Shielded Fire Alarm Jacketed Cable
Jacket Material PVC
Length 1000 ft
Mfr. # 44021004
Number Of Conductors 2
Outside Diameter 0.138 Inch
Resistance 6.5 Ohm/m At 20 deg C
Shield 0.001 IN Thick Aluminum/Mylar (Overall Shielded)
Shielding 0.001 Inch thick aluminum/mylar shield
Special Features Sequential footage markings; Sunlight Resistant
Standard UL Standards 1424, NEC Article 760 Type FPLR And UL Standards 13, NEC Article 725 Type CL2R; Flame Rating: UL 1666 (Riser), C(UL) FT4, RoHS Compliant
Standards UL 13, 1424 Listed, NEC Articles 725 and 760
Stranded/Solid Solid
Sub Brand Honeywell Cable
Temperature Rating -20 To 75
Type FPLR-CL2R
Voltage Rating 300 Volt